PostHeaderIcon munchkin boiler lights off


(3) 399M boilers lighting issues

Duration : 0:1:34


Technorati Tags: , ,

5 Responses to “munchkin boiler lights off”

  • hydronicsbob says:

    1st thing, do you …
    1st thing, do you have any manuals? I’m not sure what “reseted through the valve” means….give me a walk-through. something like, blower starts and runs for 15 seconds, then slows down, the green light comes on, it runs for about X long and there is a rumble but the boiler keeps firing…..something that describes more detailed what is happening. I will try to help.

  • mariatim2000 says:

    sorry the last line …
    sorry the last line should read:

    I am handy and was able to control the rumbling but it needs to constantly be reseted through the valve

    Thanks for any help or hints you may have

  • mariatim2000 says:

    how can someone set …
    how can someone set the high and low temps?

    I have a Munchkin installed back in 2005. Great machine till the rumbling starts. I have three zones. One main (radiators) ,one hot water,one basement (panel boards).

    I am handy and plaed

  • hydronicsbob says:

    wow I wasn’t …
    wow I wasn’t expecting a comment. I posted this for the factory to check out. What I found was on certain serial #’s, there was a “swirl plate” type piece that needed to be added between the blower/gas valve. It fixed the issue. It happens on certain 399Munchkins about 2 yrs. old now (10-9-08).

  • Chad71174 says:

    Improper gas …
    Improper gas pressure?